Perkins 2500 Series engine has been developed using the latest engineering techniques and builds on the strengths of the already very successful 2000 Series family and addresses today’s uncompromising demands within the power generation industry. Developed from a proven heavy-duty industrial base these products offer superior performance and reliability.

Perkins 2506C-E15TAG2 is a turbocharged and air-to-air chargecooled, 6 cylinder diesel engine. Its premium features provide economic and durable standby duty, exceptional power-to-weight ratio resulting in exceptional fuel consumption and low gaseous emissions and advanced overall performance and reliability making this the prime choice for today’s power generation industry.

Economic Power

Mechanically operated unit fuel injectors with advanced electronic control, combined with carefully matched turbocharging, give excellent fuel atomisation which leads to exceptional low fuel consumption.

Reliable Power

Developed and tested using the latest engineering techniques and finite element analysis for high reliability.

Low oil usage and low wear rates.

High compression ratio ensures clean rapid starting in all conditions.

Support comes from a worldwide network of 4,000 distributors and dealers.

Compact, Clean and Efficient Power

Exceptional power to weight ratio and compact size gives optimum power density for ease of installation and more cost effective transportation.

Designed to provide excellent service access for ease of maintenance.

The above ratings represent the engine performance capabilities to conditions specified in ISO 8528/1, ISO 3046/1:1986, BS 5514/1.

Derating may be required for conditions outside these; consult Perkins Engines Company Limited. Generator powers are typical and are based on an average alternator efficiency and a power factor (cos. θ) of 0.8.

Fuel specification: BS 2869: Part 2 1998 Class A2 or ASTM D975 D2. Lubricating oil: 15W40 to API CI4.

Rating Definitions

Baseload Power: Power available for continuous full load operation. Overload of 10% permitted for 1 hour in every 12 hours operation.

Prime Power: Power available at variable load with a load factor not exceeding 80% of the prime power rating. Overload of 10% is permitted for 1 hour in every 12 hours’ operation.

Standby Power: Power available in the event of a main power network failure up to a maximum of 500 hours per year of which up to 300 hours may be run continuously. Load factor may be up to 100% of standby power. No overload is permitted.

a. Excellent damping performance: optimization and design of the damping system based on dynamic computer simulations.

b. Advanced control system: the control strategy of full monitoring system based on reliability design.

c. Green environmental protection: diesel gensets integrated with energy saving and low emission.

d. Low noise: exhaust and muting system is customized for each unit.

e. Good performance: stable running, small vibration, low fuel consumption, low oil consumption, long running life and low noise.